Is the safety light curtain frequently causing temper tantrums? 6 common faults and solutions, explained in one article!

Aug 01,2025


As the "safety guard" of industrial equipment, once a safety light curtain malfunctions, it will either frequently shut down and affect production, or "fail" at critical moments and lay hidden dangers. Many factory workers have encountered this headache: why did the light curtain suddenly sound an alarm when they had just replaced the new equipment?

Today, let's take a look at the 6 common faults of safety light curtains, from symptoms to causes and solutions. We will teach you step-by-step how to quickly troubleshoot and make the production line less shut down and safer!

 

Fault 1

                                              After power on, there is no response and the indicator light does not light up


 

1、 Phenomenon:

After connecting the power, the indicator lights of the transmitter and receiver do not light up, and the device cannot enter the protective state.

 

 

2、 Possible reasons:

Power supply issues: unstable power supply voltage (such as 15% below rated voltage), broken power lines or loose connectors;

• Fuse blown: The internal circuit short circuit caused the fuse to blow;

 

• Mainboard malfunction: The core control board is damaged (such as lightning strikes, strong electrical shocks).

 

3、 Solution:

1. Use a multimeter to measure the output voltage of the power supply, ensuring it meets the rated value of the light curtain (usually 24V DC);

2. Check if the power cord connector is oxidized and replace the damaged cable;


 

3. If the fuse is blown, first check for a short circuit (such as cable breakage), and then replace it with a fuse of the same specification;

4. Are all of the above okay? Perhaps the motherboard is damaged, please contact the manufacturer for repair or replacement.


 

 

Fault 2
 

Frequent false alarms when unobstructed

 

1、 Phenomenon:

There is no object blocking the beam of light, but the light curtain repeatedly triggers protection signals (indicator light turns red, equipment stops).

 

 

2、 Possible reasons:

Environmental interference: direct sunlight, strong arc welding light, and other interference receivers;

• Lens contamination: Dust and oil stains cover the lens, causing beam attenuation to be misjudged as obstruction;

Alignment deviation: The transmitter and receiver are installed askew, and some beams are not received;

Electromagnetic interference: Electromagnetic radiation interference signals from nearby motors and frequency converters.


 

 

3、 Solution:


 

1. Wipe the lens with a dust-free cloth and clean it at least once a week (recommended once every 3 days for high dust workshops);

2. Install a shading board to block strong light, and separate the light curtain cable from the power line for wiring (spacing ≥ 30cm);

 

3. Use a laser alignment device to calibrate the installation angle, ensuring that the transmitter and receiver are completely parallel (deviation ≤ 1 °);

4. Cover the light curtain cable with a shielding layer and ground it (grounding resistance ≤ 4 Ω) to reduce electromagnetic interference.

 

Fault 3
 

No alarm or protective action after obstruction

 

1、 Phenomenon:

When using an object to block the beam of light, the light curtain indicator light does not change color, and the device still operates normally, completely "unresponsive".


 

 

2、 Possible reasons:


 

The beam is completely blocked: the transmitter or receiver lens is completely blocked by thick oil stains or metal shavings;

• Component damage: The LED of the transmitter is burnt out (some beams do not emit light), and the photosensitive component of the receiver is malfunctioning;

 

Output circuit fault: Relay contacts are stuck and output cables are disconnected, resulting in the inability to send protection signals.

 

3、 Solution:

1. Thoroughly clean the lens (stubborn oil stains can be lightly wiped with an alcohol swab) to ensure that there is no complete obstruction;

 

2. Observe the transmitter in a dark environment to see if there is a missing beam (or detect with an infrared camera), and replace the damaged LED;

3. Use a multimeter to measure the output terminal. If the signal does not change when obstructed, it may be due to a faulty relay and the output module needs to be replaced.

 

Fault 4


 

Protect signal delay and respond slowly

 


 

1、 Phenomenon:

After blocking the beam, the equipment takes 1-2 seconds to shut down, which is significantly slower than before.


 

 

2、 Possible reasons:

• Component aging: transmitter LED brightness attenuation, receiver sensitivity decrease;

Algorithm redundancy: Some old models have too many light curtain verifications, resulting in long processing times;


 

• Load delay: Downstream equipment (such as contactors and frequency converters) operates slowly and is mistakenly identified as a light curtain issue.

 

3、 Solution:

1. Use an oscilloscope to measure the response time of the light curtain (normally ≤ 50ms). If it exceeds the standard, check if the components are aging and need to be replaced;


 


 

2. Contact the manufacturer to upgrade the firmware and optimize the signal processing algorithm (some new models can reduce redundancy checks);

3. Test the action time of downstream equipment separately and replace the high-speed contactor (response ≤ 10ms).


 

 

Fault 5


 

Some areas are insensitive and have 'blind spots'

 

1、 Phenomenon:


 

Blocking the upper part of the light curtain triggers a normal alarm, but blocking the lower part does not respond, indicating a detection blind spot.

 

2、 Possible reasons:

Local component damage: One row of transmitter LEDs or receiver photosensitive components is damaged;

 

Latest News

Get A Quote

Our sales team will provide you with a detailed quotation within 24 hours.
Whether your needs are for a single product or a complete customized solution, we will provide a tailored quotation and technical support based on your specific requirements.

Deputy General Manager
Mr. Lin
Phone: 135880666646
Whatsapp: 135880666646

Sakady

Deputy General Manager
Mr. Lin

Phone: 135880666646
Whatsapp: 135880666646

Sakady
Overseas Marketing Manager
Lucia Jiang

Phone: +86 18616850611
WhatsApp: +86 18616850611

 

Sakady

Consult Now

Submit
%{tishi_zhanwei}%